Analog Value Representation For Resistance Type Transmitters; And From 150 W To 600 W; Current Measuring Ranges 0 To 20 Ma And 4 To 20 Ma - Siemens SIMATIC S7-300 Reference Manual

Programmable logic controllers module data
Hide thumbs Also See for SIMATIC S7-300:
Table of Contents

Advertisement

Table 4-14 Analog Value Representation in Current Measuring Ranges 0 to 20 mA and 4 to
20 mA
System
Dec.
Hex.
32767
7FFF
23.70 mA
32512
7F00
32511
7EFF
23.52 mA
27649
6C01
27648
6C00
20 mA
20736
5100
15 mA
1
1
723.4 nA
0
0
0 mA
–1
FFFF
–4864
ED00
–3.52 mA
–4865
ECFF
–32768
8000
Analog Value Representation for Resistance-Type Transmitters
Table 4-15 Analog Value Representation for Resistance Type Transmitters from 10 kW

and from 150 W to 600 W

System
10 kW
Dec.
Hex.
32767
7FFF
11.852
kW
32512
7F00
32511
7EFF
11.759
kW
27649
6C01
27648
6C00
10 kW
20736
5100
7.5 kW
1
1
361.7mW
0 W
0
0
Programmable Logic Controllers S7-300 Module Data
A5E00105505-03
Current Measuring Range
0 to 20 mA
22.96 mA
22.81 mA
20 mA
16 mA
4 mA + 578.7 nA
4 mA
1.185 mA
Resistance-Type Transmitter Range
150 W
300 W
177.77W
355.54 W 711.09 W Overflow
150.01
300.01 W 600.02 W
W
176.38
352.77 W 705.53 W Overrange
W
150 W
300 W
112.5 W
225 W
5.43 mW
10.85
mW
0 W
0 W
(negative values physically
(negative values physically
not possible)
4 to 20 mA
Overflow
Overflow
Overrange
Overrange
Rated range
Rated range
Underrange
Underrange
Underflow
Underflow
600 W
600 W
450 W
21.70
Rated range
mW
0 W
Underrange
Analog Modules
4-15