Siemens SIMATIC S7-300 Reference Manual page 202

Programmable logic controllers module data
Hide thumbs Also See for SIMATIC S7-300:
Table of Contents

Advertisement

Digital Modules
Technical data of the SM 327; DI 8/DX 8 x DC 24 V/0.5 A, parameterizable
Dimensions and Weight
Dimensions W x H x D
(in millimeters)
Weight
Data for Specific Module
Supports clocked
operation
Number of inputs
Number of inputs/outputs
Length of cable
Unshielded
Shielded
Voltages, Currents, Potentials
Rated load voltage L+
Number of inputs that can be
triggered simultaneously
Horizontal configuration
Up to 60 _C
Vertical configuration
Up to 40 _C
Total current of the outputs
(per group)
Horizontal configuration
Up to 40 _C
Up to 60 _C
Vertical configuration
Up to 40 _C
Isolation
Between channels and
backplane bus
Between the channels
Permitted potential difference
Between the different
circuits
Insulation tested with
Current consumption
From the backplane bus
From load voltage L+
(without load)
Power dissipation of the module typ. 3 W
Status, Interrupts, Diagnostics
Status display
Interrupts
Diagnostic functions
3-118
40 x 125 x 120
Approx. 200 g
No
8 digital
8 single,
parameterizable
max. 600 m
max. 1000 m
24 VDC
16
16
max. 4 A
max. 3 A
max. 2 A
Yes
No
75 VDC / 60 VAC
500 VDC
max. 60 mA
max. 20 mA
Green LED per channel
None
None
Data for Selecting a Sensor
Input voltage
Rated value
For signal "1"
For signal "0"
Input current
At signal "1"
Input delay
At "0" to "1"
At "1" to "0"
Input characteristic curve
Connection of Two-Wire
BEROs
Permitted bias current
Data for Selecting an Actuator
Output voltage
At signal "1"
Output current
At signal "1"
Rated value
Permitted range
At signal "0"
(leakage current)
Output delay (for resistive load)
At "0" to "1"
At "1" to "0"
Load resistor range
Lamp load
Parallel connection of
2 outputs
For redundant triggering of
a load
To increase performance
Triggering a digital input
Switch rate
For resistive load
Inductive load according to
IEC 947-5-1, 13 DC
For lamp load
Limit (internal) of the inductive
circuit interruption voltage up
Short-circuit protection of the
output
Threshold on
Programmable Logic Controllers S7-300 Module Data
24 VDC
15 to 30 V
–30 to 5 V
typ. 6 mA
1.2 to 4.8 ms
1.2 to 4.8 ms
According to
IEC 61131, type 1
Possible
max. 1.5 mA
min. L + (– 1,5 V)
0.5 A
5 mA to 0.6 A
max. 0.5 mA
max. 350 ms
max. 500 ms
48 W to 4 kW
max. 5 W
Possible
Not possible
Possible
max. 100 Hz
max. 0.5 Hz
max. 10 Hz
typ. L + (–54 V)
Yes, electronic
1 A, typ.
A5E00105505-03