Appendix C: Default Settings

16.1 Alarm Setpoints

The default settings for the alarm setpoints are the following:
5, 20, and 50 percent of full-scale range, except for R123, which are 1, 2, and 5 percent of full-
scale range
Non-latching
Horn and strobe (if applicable) enabled

16.2 Relays

The default setting for the internal fault relay is the energized state. All other relays (alarm, warning,
caution, and horn) are set to de-energized.

16.3 Output

The default setting for digital output is None. The factory default settings for analog output are 3.5 mA
for Warm-up and 2.0 mA for Fault.
Chillgard 5000
Appendix C: Default Settings
US
78