Command Specifications
Remarks
Command
OPEN_SYSTEMEX
Purpose
Code
Argument
Response code
Remarks
To issue this command, the setting areas of the software table and data rate
must be set.
Open the CompoNet Master Board, and let it be ready to be used.
0x0002
Function
1-WORD data,
specification
Set 1 (ON) to enable or 0 (OFF) to disable.
Bit
0
Communications stop due to communications error
function
1
I/O communications manual startup function
2
IN data zero clear due to communications error
function
3 to 7
Reserved area, Set 0 (OFF).
8
Registration Table function
9
Logical error checking item function
10
Network parameter function
11
Slave-Unit parameter function
12 to 15
Reserved area, Set 0 (OFF).
Normal end: 0x0000
At an error:
Hardware error: 0x8101 to 0x8109
Error of argument data format: 0xC000+Bit location of an error
Bit
0
Software table
1
Data rate
2 to 7
Reserved area, Set 0 (OFF)
8
Registration Table function
9
Logical error checking item function
10
Network parameter function
11
Slave-Unit parameter function
12 to 15
Reserved area, Set 0 (OFF)
Errors in argument data format refer to the format errors in the relevant setting
area.
To issue this command, the following setting areas must be set:
[Mandatory]
Software table
Data rate
[Required when the relevant function is enabled or when the relevant function
needs the setting]
Logical error checking item
Registration Table
Description
Error location
Section B-4