Adjustment Procedures For Interference Light - Mitsubishi Electric AJ65BT-RPI-10A User Manual

Cc-link system space optical repeater module
Table of Contents

Advertisement

4.6.3 Adjustment procedures for interference light

The following is the adjustment procedures for interference light emitted
from the other system.
(1) Influence of interference light between module A1 and A2
(a) Turn on the module A1 and A2 only and turn off the module B1
and B2.
(b) Check for influence of interference light emitted from A1 to A2
1) When the operation indicator LED, R1 of A2 is off:
No influence of interference light is identified.
2) When the operation indicator LED, R1 of A2 is on:
The influence of interference light is identified.
Readjust the optical axis of module A1 by making it away
from the system (2).
(c) Check for influence of interference light emitted from A2 to A1
1) When the operation indicator LED, R1 of A1 is off:
No influence of interference light is identified.
2) When the operation indicator LED, R1 of A1 is on:
Influence of interference light is identified.
Readjust the optical axis of module A2 by making it away
from the system (1).
Check that
R1 is off.
R
Module A1
System
(1)
Interference
(ON)
System
(2)
Module B2
(OFF)
30
Module B1
(OFF)
light
Module A2
(ON)
R
Check that
R1 is off.