Mitsubishi Electric AJ65BT-RPI-10A User Manual page 35

Cc-link system space optical repeater module
Table of Contents

Advertisement

(3) When using multiple sets of the AJ65BT-RPI-10A/10B in line,
provide shields between the sets. Not doing so can cause a
malfunction due to interference.
(4) When using multiple sets of the AJ65BT-RPI-10A/10B in parallel,
place the A and B modules alternatively and keep a distance of at
least 1m (3.28ft.). Not placing them alternately can cause a
malfunction due to interference.
Referring to the figure showing the relation between the optical
communication distance and the distance from the other system,
adjust the optical axis to remove the influence of interference light.
(Refer to Section 4.6.3.)
1
*1
A value obtained when the optical axis of each system is adjusted to nearly
the center of the area in which the operation indicator LED, R3 turns on.
*2
A value obtained when the optical axis of the system is slanted toward the
other system.
Shield needed
A module
1m (3.28ft.)
Install modules alternately and keep
at least
a distance of at least 1m (3.28ft.)
B module
8
Adjustment for interference
light not required
4
0
0
10
Optical communication distance (m)
B module
A module
for interference
light required
(Worst-case value *2)
Adjustment for
interference light
required (Normal value *1)
Not used
50
20
Adjustment
100