Daikin DPS Installation And Maintenance Manual page 75

Microtech iii unit controller for rebel commercial packaged rooftop systems
Table of Contents

Advertisement

Suction Line Refrigerant Temperature
Sensor Problem – (SRT Sensor: Problem)
This alarm occurs when the SRT sensor input is shorted or open
circuited for the Sensor Alarm Delay (default 30 seconds) . It can
also occur if the input is outside the range of -47°F to 194°F .
When this alarm is active compressor cooling and heating
operation are disabled .
The alarm must be manually cleared once corrective action is
taken .
High Inverter Compressor Discharge Line
Temperature Problem – (Hi DL Temp:
Problem)
This alarm occurs when the High Discharge Line Temperature
Unloading function has forced compressor operation to the
Standby state for a third time in a 100 minute period .
When this alarm is active compressor cooling and heating
operation are disabled .
The alarm must be manually cleared once corrective action is
taken .
Expansion Valve Problem – (Exp Valve:
Problem)
This alarm occurs when the IFB communication board detects
a faulty or disconnection between an expansion valve (EVI or
EVO) and the expansion valve control board (EVB) .
When this alarm is active compressor cooling and heating
operation are disabled .
The alarm must be manually cleared once corrective action is
taken .
NOTE: The EVB only detects a change in the EVI or EVO
condition upon power up of the EVB .
Outdoor Fan Problem – (OA Fan:
Problem)
On a single outdoor fan unit this alarm occurs when compressor
operation is forced to the Standby state due to an outdoor fan
internal fault for a third time in a 30 minute period .
On a two outdoor fan unit this alarm occurs when compressor
operation is forced to the Standby state due an outdoor fan 2
internal fault for a third time in a 30 minute period . Note that
outdoor fan 2 in this configuration provides critical cooling for the
inverter/outdoor fan control boards .
When this alarm is active compressor cooling and heating
operation are disabled .
The alarm must be manually cleared once corrective action is
taken .
www .DaikinApplied .com
Low Refrigerant Charge Problem – (Lo
Charge: Problem)
During compressor cooling operation this alarm occurs when the
indoor expansion valve (EVI) is fully open (greater that 95%),
the super heat is well above set point (greater than 20°F) and
the lower of the two discharge line temperature inputs (DRT1
and DRT3) is hot (greater than 150°F) for more than 30 minutes
continuously .
During compressor heating operation this alarm occurs when the
outdoor expansion valve (EVO) is fully open (greater that 95%)
and the super heat is well above set point (greater than 20°F) for
more than 60 minutes continuously .
When this alarm is active compressor cooling and heating
operation are disabled .
The alarm must be manually cleared once corrective action is
taken .
Refrigerant Charge Loss Problem –
(ChargeLoss: Problem)
This alarm occurs when both the suction and discharge
line pressure inputs (PTS and PTD) remain below 10 psi
continuously for 5 seconds .
When this alarm is active compressor cooling and heating
operation are disabled .
The alarm must be manually cleared once corrective action is
taken .
Suction Line Refrigerant Pressure Sensor
Problem – (PTS Sensor: Problem)
This alarm occurs when the suction line pressure inputs (PTS)
remains above 256 psi continuously for 12 minutes or below -15
psi continuously for 10 seconds .
When this alarm is active compressor cooling and heating
operation are disabled .
The alarm must be manually cleared once corrective action is
taken .
Discharge Line Refrigerant Pressure
Sensor Problem – (PTD Sensor: Problem)
This alarm occurs when the suction line pressure inputs (PTD)
remains above 611 .6 psi or below 1 .42 psi continuously for 10
seconds .
When this alarm is active compressor cooling and heating
operation are disabled .
The alarm must be manually cleared once corrective action is
taken .
75
OM 1141-3 • MICROTECH UNIT CONTROLLER
a
larMs

Advertisement

Table of Contents
loading

Table of Contents