Daikin DPS Installation And Maintenance Manual page 14

Microtech iii unit controller for rebel commercial packaged rooftop systems
Table of Contents

Advertisement

Figure 9: Commission Unit – Keypad/Display Menu Structure
See page 34 — 58
Commission Unit
Unit Set-Up
Timer Settings
SAF Set-Up
RF/EF Set-Up
Htg/Clg ChgOvr Set-Up
Cooling Set-Up
INV Cmp Set-Up
Var Cmp Set-Up
Econo Set-Up
Min OA Set-Up
Heating Set-Up
OA Fan Set-Up
Exp Valve Set-Up
Defrost Set-Up
Dehum Set-Up
Energy Rec Set-Up
Head Pressure Set-Up
Evap Cond Set-Up
D3 Set-Up
Alarm Configuration
List continues
on, page 16
See page 42 — 44
INV Cmp Set-Up
COMPRESSOR STATUS
Clg State= ____________
Htg State= ____________
INV Cmp Spd= XXX .X%
INV Spd Cmd= XXX .X%
Comp 3=_____________
Prev Standby=_______
Compressor Limiting
Fault Code Details
INV Port Temp= XXX .XºF
INV Fin Temp= XXX .XºF
INV Cmp Amps= XX .XA
REFRIG CIRCUIT STATUS
PTD= XXX .Xpsi
PTS= XXX .Xpsi
4 Way Valve=__________
RcvrSol Valve=_________
BP Sol Valve=_________
1, 2 See the expansion
page 21
information on
OM 1141-3 • MICROTECH UNIT CONTROLLER
See page 34
See page 34 —
35
Unit Set-Up
Timer Settings
Apply Changes= No
Service Time= 0min
RAT Sensor= Yes
Start Up= 180s
OAT Sensor= Yes
Recirculate= 180s
Space Sensor= Digtl/Net
Zero OA Time= 0min
Eng Units= English
Tnt Override= 120min
Unit Name= xxxxxxxxxxxx
Post Heat= 0s
Rapid Start= No
Pwd Timeout= 10min
Rapid Start Tm= 10min
Low DAT= 6min
DO10 Clg= FanOp
ClgStateDelay= 300s
Bypass Valve= 300s
Clg Stg Time= 5min
Htg Stg Time= 5min
Air Flw Ign= 120s
MinExStrtTm= 120s
MinExStopTm= 120s
ER Whl Stg Tm= 5min
ER Whl Off Tm= 20min
EvCnd Stg Tm= 10min
WRV Init Tm= 60s
Min WRV Time= 60s
Htg Wrmup Tm= 240s
Htg Hld Period= 240s
RH Srg Time= 10min
Srvc Time Inc= 20s
OffHtCIDelay= 120s
COMPRESSOR SETUP
Clg Lo OAT Lk=
55°F (RTU/SCU)
0°F (MPS)
25°F (DPS)
Htg Lo OAT Lk=
0 .0ºF
45°F (100% OA w/o ER)
1
Htg Hi OAT Lk= 55 .0ºF
EffHtgOATLk= _______ºF
OAT Diff= 2ºF
INV Period= 20s
INV Gain= 2 .5
INV PAT= 10s
INV Max Chg= 15%
2
IFB COMM STATUS
See page 36 — 38
SAF Set-Up
SAF Ctrl= DSP
AplyInputChgs= No
CO2 Input= None
CFM Input= None
BSP Input= No
SPEED CONTROL
Rem SAF Cap= 33%
DSP CONTROL
DSP DB= 0 .1in
VFD Ramp Time= 60s
Min Period= 5s
Max Spd Chg= 15%
Duct Press 1= X .Xin
Duct Press 2= X .Xin
1 ZONE VAV CONTROL
Min Clg Spd= 40%
Max Clg Spd= 100%
Min Htg Spd= 40%
Max Htg Spd= 100%
Space Period= 60s
Space Gain= 0 .8
Space PAT= 400s
Space Max Chg= 10%
Var Comp Set-Up
COMPRESSOR STATUS
Var Cmp Status= _______
Var Spd Cmd= _________
Comp 1= _____________
Comp 3= _____________
Comp 5= _____________
REFRIG CIRCUIT STATUS
PTD1= _______________
PTD2= _______________
VCmpDischSH= _______
C1DschSatTmp= _______
C2DschSatTmp= _______
DRT1= _______________
DRT2= _______________
Cond Sol 1= Off
Cond Sol 2= Off
COMPRESSOR SET-UP
Var Cmp Period= 20s
Date/Time
Var Cmp Gain= 1
MM/DD/YYYY HH:MM:SS
Var Cmp PAT= 40s
VarCmp MaxChg= 10%
Compressor Limiting
OilBoost= Off
Clg Press Lmtg=_______
LowOilTime= 10min
Htg Press Lmtg=_______
OilBoostTime= 15min
C Ratio Lmtg=_________
LowTcOAT= 80°F
Ref DLT Lmtg=_________
INV Brd Lmtg=_________
INV Man Dsbl= Enable
Comp3 ManDsbl= Enable
14
K
/d
M
s
eypad
Isplay
enu
tructure
CO
CONTROL
BSP CONTROL
2
Min PPM= 0PPM
BSP DB= 0 .01in
Max PPM= 2000PPM
BSP Period= 5s
V/A @ Min PPM= 0V
BSP Gain= 0 .2
V/A @ Max PPM= 10V
Max Spd Chg= 4%
Min SAF PPM= 800PPM
SAF SETUP
Max SAF PPM= 1100PPM
SAF Ctrl Dly= 30s
Min PPM Spd= 50%
Min Speed= 33%
Max PPM Spd= 100%
VAVBox Out= _________
CFM CONTROL
Max SAF Hz=
Min CFM= 0CFM
Max Vent Speed= 100%
Max CFM= 10000CFM
Max SAF RPM= 2600
V/A @ Min CFM= 0V
ECM Status= __________
V/A @ Max CFM= 10 V
SAF CFM DB= 3%
SAF CFM Period= 30s
SAF CFM Gain= 0 .1
SAF CFM MxChg= 5%
See page 45
Econo Set-Up
EconChgovr= Enth&DB
Econo FDD= On
Clg Stage Time= 5min
Chgover Temp= 55 .0°F
Clg DB= 2 .0°F
Econo Period=
30/40s (air/water)
Econo Gain=
1-Oct (air/water)
Econo PAT=
60/40s (air/water)
Econo Max Chg=
10/15% (air/water)
Flush Econo= Yes
Econo Diff= 2 .0°F
EWT Diff= 3 .0°F
Clg Reset= None
Min Clg Spt= 55 .0°F
Min Clg Spt @= 0/NA
Max Clg Spt= 65 .0°F
Max Clg Spt@= 100/NA
Max OAT Lmt= 75°F
Min OAT Lmt= 70°F
Calibrate OAD= No
PosSwOpen= 97%
Max Sw Diff= 3%
PosSwClose= 3%
Min SW Diff= 5%
OAD Sw Status= _______