OA CFM Max Chg is an adjustable item which sets the
"maximum step" used in the control function that modulates
the Min OA Pos parameter to maintain the OA Flow parameter
at the MinOA Flow set point when a unit is equipped with the
optional DesignFlow outdoor airflow measuring feature, or a
field supplied OA measuring station.
Min Clg Spd is an adjustable item that sets the discharge fan
speed on a VAV unit at which the Ventilation Limit reaches the
LoFloVent= value .
Des Clg Spd is an adjustable item used to adjust the design
cooling speed set point .
MinRFEFTm is an adjustable item used to set the time period
for which the return/exhaust fan must operate at the minimum
speed before the building static pressure override function is
activated .
BSPOvdST an adjustable item which sets the "sampling time"
used in the PI control function used for the building static
pressure override feature .
BSPOvdGain is an adjustable item which sets the "Gain" used
in the PI control function used for the building static pressure
override feature .
BSPOvdMxChg is an adjustable item that sets the maximum
value for an increase or decrease of the outside air damper
position due to the building static pressure override feature .
OM 1141-3 • MICROTECH UNIT CONTROLLER
ResetTLmt is an adjustable item which sets a temperature low
limit which overrides functions that reset the outside air damper
position if the temperature gets too cold .
RstTSmplT an adjustable item which sets the "sampling time"
used in the PI control function used for the Reset Temperature
Limit feature .
RstTGain is an adjustable item which sets the "Gain" used in
the PI control function used for the Reset Temperature Limit
feature .
RstTPAT is an adjustable item which sets the "project ahead
time" used in the PI control function used for the Reset
Temperature Limit feature .
RstTMaxChg is an adjustable item that sets the maximum
change value PI loop used for the Reset Temperature Limit
feature .
Min Inc Rate is an adjustable item used to set the minimum
increase rate for the outside air damper "cold start" sequence .
Max Inc Rate is an adjustable item used to set the maximum
increase rate for the outside air damper "cold start" sequence .
0-30% OA Max is an adjustable item used to set the maximum
outside air damper position when the unit is configured for a
30% damper .