Microtech iii unit controller for rebel commercial packaged rooftop systems
Table of Contents

Advertisement

Unit State is a status only item which indicates the state of
operation in which the unit is currently operating . The unit can
be in any of the operating states shown .
Unit Status is a status only item which indicates the status
of operation in which the unit is currently operating . The unit
status can be any of the status values shown .
Dehum Status is a status only item which indicates the status
of operation of the dehumidifier. The dehumidifier can be active
or inactive .
Ctrl Mode is an adjustable item which sets the operating mode
of the unit . The unit can be in any of the modes shown .
Clg Status is a status only item which indicates whether or not
mechanical cooling is currently allowed . If cooling is disabled,
the reason is indicated .
Htg Status is a status only item which indicates whether or not
heating is currently allowed . If heating is disabled, the reason is
indicated . If the unit is a heat pump, this applies to compressor
heat .
Supl Htg Status (Heat Pump only) is a status only item which
indicates whether or not supplemental heating is currently
enabled . If supplemental heating is disabled the reason is indicated.
Econo Status is a status only item which indicates whether
or not the economizer is currently enabled . If economizer is
enabled, the reason is indicated .
Clg Capacity is a status only item which indicates the
percentage of the unit maximum cooling capacity currently
operating .
Htg Capacity is a status only item which indicates the
percentage of the unit maximum heating capacity currently
operating . If the unit is a heat pump, this applies to the
compressor heat .
OM 1141-3 • MICROTECH UNIT CONTROLLER
Supl Htg Cap (Heat Pump only) is a status only item which
indicates the percentage of the unit maximum supplemental heating
capacity currently operating.
Reheat Capacity is a status only item which indicates the
percentage of the unit maximum reheat capacity currently
operating .
SAF Capacity is a status only item which indicates the
capacity of the supply air fan .
RF/EF Capacity is a status only item indicating the capacity of
the return fan/exhaust air fans .
OAD/EconoCap is a status item which indicates the
percentage that the outdoor damper is currently open .
Rel Humidity is a status only item that displays the current
relative humidity reading from the optional humidity sensor .
Net Emrg Ovrd is an adjustable item which indicates if the
unit was shut down in an emergency situation via a network
command .
Net App Mode is a network adjustable item which indicates
that the unit is set for network off, cooling only, heating only,
fan only or auto heating/cooling operation via a network signal .
This item has no affect on the unit operation unless the Ctrl
Mode item is set to "Auto ."