OA Fan Period is an adjustable item that sets the sample
period for the PI loop used to control the outdoor fans in the
cooling mode of operation to maintain the EffDshSatTSpt .
OA Fan Gain is an adjustable item that sets the Gain for the PI
loop used for the PI loop used to control the outdoor fans in the
cooling mode of operation to maintain the EffDshSatTSpt .
OA Fan PAT is an adjustable item that sets the project ahead
time for the PI loop used for the PI loop used to control the
outdoor fans in the cooling mode of operation to maintain the
EffDshSatTSpt .
INVAlarmCode is a status only item which displays the active
inverter fault code . The INV Comp: Problem alarm is generated
when a fault code is active .
Code Text is a status only item which displays a text
description of the active inverter fault code .
OF1AlarmCode is a status only item which displays the
active outdoor fan 1 fault code . The OA Fan: Problem alarm is
generated related to a fault code being active .
Code Text is a status only item which displays a text
description of the active outdoor fan 1 fault code .
OF2AlarmCode is a status only item which displays the
active outdoor fan 2 fault code . The OA Fan: Problem alarm is
generated related to a fault code being active .
Code Text is a status only item which displays a text
description of the active outdoor fan 2 fault code .
OM 1141-3 • MICROTECH UNIT CONTROLLER
PrvINVAlmCode is a status only item which displays the most
recent inverter fault code that was active .
Code Text is a status only item which displays a text
description of the previous inverter fault code .
MM/DD/YYYY HH:MM:SS is a status only item which displays
the time stamp of the previous inverter fault code .
PrvOF1AlmCode is a status only item which displays the most
recent outdoor fan 1 fault code that was active .
Code Text is a status only item which displays a text
description of the previous outdoor fan 1 fault code .
MM/DD/YYYY HH:MM:SS is a status only item which displays
the time stamp of the previous outdoor fan 1 fault code .
PrvOF2AlmCode is a status only item which displays the most
recent outdoor fan 2 fault code that was active .
Code Text is a status only item which displays a text
description of the previous outdoor fan 2 fault code .
MM/DD/YYYY HH:MM:SS is a status only item which displays
the time stamp of the previous outdoor fan 2 fault code .