RF/EF Spd Cmd is an adjustable item for units with variable
speed supply air fan on the return/exhaust fans that sets the
speed of the return/exhaust fan .
OAD/Econo is an adjustable item which is used to set the
economizer damper position .
GasHtgOnOff is an adjustable item used to turn the gas heat
enable output On and Off .
Htg Valve is an adjustable item used to manually drive the
modulating heating valve open and closed .
SCR Out is an adjustable item used to manually drive the
output signal to the SCR .
Htg Stg 1 is an adjustable item that turns on the first stage of
heat on units equipped with staged heating .
SCR Ena 1 is an adjustable item that enables the SCR heater .
Htg Stg 2 is an adjustable item that turns on the second stage
of heat on units equipped with staged heating .
Htg Stg 3 is an adjustable item that turns on the third stage of
heat on units equipped with staged heating .
Htg Stg 4 is an adjustable item that turns on the fourth stage of
heat on units equipped with staged heating .
Reheat Valve is an adjustable item used to manually drive the
reheat valve open and closed .
ERec Wheel is an adjustable item which is used to turn on/off
the energy recovery wheel output .
ERec Whl Cmd is an adjustable item is an adjustable item
which is used to set the energy recovery wheel variable speed
supply air fan speed .
www .DaikinApplied .com
ERBP Dmpr Cl is an adjustable item which is used to close the
energy recovery bypass damper .
ERBP Dmpr OP is an adjustable item which is used to open
the energy recovery bypass damper .
Alm Output is an adjustable item which is used to turn on/off
the alarm output .
FanOp is an adjustable item which is used to turn on/off the
fan operation output .
When Manual Control is set to ManCtrl, the Control Mode is
set to Off so that the unit will not restart automatically . When
Manual Control is set to Normal all digital outputs in the Manual
Control menu are set to Off and all the analog outputs are set
to 0 .0% so that all outputs are in the Off or minimum position
when Manual Control is set to ManCtrl
61