8.3 Output Specifications

Number of output point
Insulation method
Output type
Output capacity
Output mode (OUT1/OUT2)
Pulse width
Pulse by
Pulse output
integral power
unit
Type
Alarm
Event
Alarm reset
Protection element
*1 Varistor is mounted internal as a protection element.
Install a protective device in case of using at the place where it effects by surge.
<Internal output circuit>
How to calculate
Unit for pulse output>(Max. measurement power [kW])/(3600[s]×1 [pulse/s])
Note
(1) Improper unit setting may cause miss counting.
(2) If the OFF time is too short, there is a possibility of counting errors.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
2 points *Insulate between output terminals
PhotoMOS relay
1a
100mA, 30V AC/DC
・Pulse by integral power
・Output by alarm or events
Approx. 100ms
0.0001kWh/ 0.001kWh/ 0.01kWh/ 0.1kWh/
1kWh/ 10kWh/ 100kWh
Stand-by alarm/ Under voltage alarm/ Over voltage alarm/
Power interruption alarm/ Under current alarm/
Over current alarm/ Active power alarm/ Reactive power alarm/
Apparent power alarm/ PF alarm/ Over frequency alarm/
Under frequency alarm/ Voltage harmonics alarm/
Current harmonics alarm/ Voltage THD alarm/
Current THD alarm/ Unbalanced voltage alarm/
Unbalanced current alarm/
Power demand alarm/ Current demand alarm/ counter output/
level output (external control)
Self-reset (according to the setting) / Manual-reset
Varistor *1