4.4 How to Set

■Set before measuring.
Select setting item with <ITEM/△> and press <SET>, and the value will be blinking.
Set with <ITEM/△> and <SHIFT/▽>.
When you select [YES] with the confirmation window and press <SET>, the setting values are
settled.

4.4.1 Settings for power measurement

Phase/Wire system
Select phase/wire system to measure.
Press <ITEM/△>, <SHIFT/▽> to select phase/wire system.
[Set list] 1P2W, 1P3W, 3P3W, 3P4W (initial: 1P2W)
* When the system is not matched with the measure system, it doesn't measure correctly.
CT type
Select using CT type (secondary side current).
To use CT with secondary side current 5A; [5]
To use CT with secondary side current 1A: [1]
Primary side current of CT
Set the primary side current of using CT.
Enter the primary side current of CT that is set at CT type setting.
Primary side current of using CT is 400A: [400]
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Press <ITEM/△>, <SHIFT/▽> to set.
[Set range] 1 to 65535 (initial:5)
Increase
decrease
Press <ITEM/△>, <SHIFT/▽> to select CT type.
[Set list] 5 (5A), 1 (1A) (initial: 5)