Panasonic KW9M User Manual page 48

Eco-power meter advanced type
Hide thumbs Also See for KW9M:
Table of Contents

Advertisement

Voltage harmonics alarm threshold (OUT1 OUT2)
Set a value of voltage harmonics to use for alarm output.
When one of 2 to 31-order harmonics exceeds the setting threshold, it output alarm.
Voltage harmonics alarm OFF threshold (OUT1 OUT2)
Set a value of voltage harmonics to clear the alarm output.
When all values of 2 to 31-order harmonics falls below the setting threshold, it clear the alarm
output.
Current harmonics alarm threshold (OUT1 OUT2)
Set a value of current harmonics to use for alarm output.
When one of 2 to 31-order harmonics exceeds the setting threshold, it output alarm.
Current harmonics alarm OFF threshold (OUT1 OUT2)
Set a value of current harmonics to clear the alarm output.
When all values of 2 to 31-order harmonics falls below the setting threshold, it clear the alarm
output.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
* It is only when [AL-VH] is selected for unit for pulse output.
Press <ITEM/△>, <SHIFT/▽> to set.
[Set range] 0.00 to 400.00 [%] (initial: 400.00)
Increase
decrease
* It is only when [AL-VH] is selected for unit for pulse output.
Press <ITEM/△>, <SHIFT/▽> to set.
[Set range] 0.00 to 400.00 [%] (initial: 400.00)
Increase
decrease
* It is only when [AL-CH] is selected for unit for pulse output.
Press <ITEM/△>, <SHIFT/▽> to set.
[Set range] 0.00 to 400.00 [%] (initial: 400.00)
Increase
decrease
* It is only when [AL-CH] is selected for unit for pulse output.
Press <ITEM/△>, <SHIFT/▽> to set.
[Set range] 0.00 to 400.00 [%] (initial: 400.00)
Increase
decrease
41