6.2.11 Current
・The present current value is displayed. (N-phase current is displayed for 3P4W.)
・It measures from 0.1% of CT secondary current.
・When input current exceeds 200% or the display range, it displays "- - - - -".
Check and confirm the measurement environment.
・Current measuring points
Display
st
1
1
circuit R-current
nd
2
2
circuit R-current
rd
3
3
circuit R-current
A
N
6.2.12 Voltage
・The present voltage is displayed.
・Press <SHIFT/▽> to change phase voltage and line voltage.
(Line voltage is not displayed for 1P2W system. Phase voltage is not displayed for 3P3W system.
Phase voltage
・When input voltage is under 3V (when VT ratio is 1.), it displays "0.0" and doesn't measure.
・When input voltage exceeds 600V or the display range, it displays "- - - - -".
Check and confirm the measurement environment.
・Voltage measuring points
Display
1P2W
R-voltage (L1-N)
1
st
or 1
circuit R-voltage
None or
2
nd
2
circuit R-voltage
None or
3
rd
3
circuit R-voltage
A
Average
1 2
2 3
No display
3 1
A
Average
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Eco-POWER METER measures the current as below.
1P2W
Average
-
Line voltage
Eco-POWER METER measures the voltage as below.
1P3W
R-voltage (L1-N)
None
T-voltage (L3-N)
Average of R and T
R-voltage (L1-N)
T-voltage (L3-N)
TR-voltage (L3-L1)
Average of R and T
1P3W
R-current
N-current
T-current
Average of R and T
-
3P3W
No display
RS-voltage (L1-L2)
ST-voltage (L2-L3)
TR-voltage (L3-L1)
Average
82
3P3W
3P4W
R-current
S-current
T-current
Average
N-current *only 3P4W
3P4W
R-voltage (L1-N)
S-voltage (L2-N)
T-voltage (L3-N)
Average
RS-voltage (L1-L2)
ST-voltage (L2-L3)
TR-voltage (L3-L1)
Average