3.4 For Input Connection

●Pulse input
・Contact input
Use highly reliable metal plated contacts. Since the contact's bounce time leads directly to error in
the count value, use contacts with as short a bounce time as possible. In general, select 30Hz for
max.counting speed.
・Non-contact input (Transistor input)
Connect with an open collector. Use the transistor with the following specifications.
V
=20V min. I
=20mA min. I
CEO
C
Use transistors with a residual voltage of less than 3V when the transistor is ON.
*`Short-circuit impedance should be less than 1kΩ.
Open-circuit impedance should be more than 100kΩ.
(When the impedance is 0Ω, drain current is approx. 10mA.)
・Input wiring
Please wire as short as possible by using a shielded wire or a metallic electric wire tube individually.

3.5 For Output Connection

●PhotoMOS relay output
・It adopts PhotoMOS relay output, there is no polarity.
Output: Rated capacity 30V AC/DC, 0.1A
・Do not connect devices that voltage or load exceeds the rated capacity (30V AC/DC,0.1A)
・Please wire less than 100m fir output.
If it is long, it may not work correctly due to floating capacitance.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
=6μA max