Defining Alarms - ABB SREA-01 User Manual

Ethernet adapter module
Hide thumbs Also See for SREA-01:
Table of Contents

Advertisement

85
You can select whether to send alarms by SMS, E-mail and SNMP by selecting
'Disable' or 'Enable' on the dropdown menus. If you have configured an FTP server
on the FTP setup page, you can also select to send alarm status by FTP.
Acknowledge function can be used to prevent sending multiple messages in case of
a repetitive alarm. If the acknowledge function is enabled, the user has to log in and
acknowledge the alarm on the Alarm list page before being able to receive further
messages regarding that alarm. The default is that the acknowledge function is
disabled, meaning that the user will receive a message every time when the alarm
becomes active.

Defining alarms

To add or edit an alarm point, click on the 'add alarm parameter' or 'edit' button in the
Alarm Configuration list. This will bring you to the following screen. Here you need to
select which parameter to use, and define the trigger operation that will activate the
alarm. You also need to define some properties like alarm class (1–10), and which
strings should be in the subject and message field of SMS/E-mail alarms.
Device – The drive that is being monitored. Alternatively you can use the internal
registers to trigger the alarm. This is useful if you want to trigger the alarm by
external inputs of SREA-01.
Group / Parameter – The parameter of the drive or SREA-01 to monitor.