8.4.19
6ES5 482-4UA11 Digital
Input/Output Module
Rated supply voltage L+
Rated input voltage
Inputs
Number of inputs
Isolation
Input voltage
for logic 0
for logic 1
Rated input current
Delay time
Input resistance
Coincidence factor (total load capability)
Permissible line length
Supply voltage for 2-wire BERO
Power supply
Digital section from system bus
Outputs
Number of outputs
Isolation
Fusing
Output voltage
for logic 1
for logic 0
Switching current
(resistive, inductive load)
Switching frequency
with resistive load
with inductive load
Breaking voltage (inductive)
Total switching current
Coincidence factor (total load capability)
ventilated
not ventilated
Permissible line length
Current consumption from L+/L-
Short-circuit monitoring
Indicator for signalling output (H+)
Output voltage
referred to L- (supply of 1L+)
for logic 1
for logic 0
Switching current
Enable input (F+/F-)
Voltage test to VDE 0160
Mechanical specifications
Dimensions (W x H x D)
Weight
8 - 72
24 V DC
24 V DC
16 min., 24 max.
Yes, 1 group of 32 inputs/outputs
- 33 to 5 V
13 to 33 V
8.5 mA typical
0.3 ms typical
2.8 kilohms typical
100 %
50 m max.
22 V to 33 V
5 V, 80 mA typical
8 min., 16 max., short-circuit protected
Yes
6.3 A slow,
1 fuse per 8 outputs
L+ - 1.5 V min.
3 V max.
5 mA to 0.5 A
120 Hz max.
2 Hz max. at 0.3 A, 0.5 Hz max. at 0.5 A
Limited to L+ and - 27 V
4 A max. per 8 outputs
100 %
50 %, 100 % up to 35
400 m max.
24 V, 150 mA typical
Red LED for every 8 outputs
1L+ - 5 V min.
3 V max.
10 mA max. current limiting
Jumper in front connector
Between group and ground point: 1250 V AC
20 mm x 255 mm x 195 mm
Approx. 0.4 kg
1) Short-circuit protection responds at line resistance ≤ 15 ohms
1)
o
C
System Manual
C79000-B8576-C199-03

Hide quick links: