Siemens S5-155U System Manual page 450

Hide thumbs Also See for S5-155U:
Table of Contents

Advertisement

The 465 Analog Input Module
voltage/current
8 channels
channel 4 - 7
with
16 channels channel 8 - 15
broken wire
8 channels
channel 0 - 3
detection
16 channels
channel 0 - 7
two's complement
8 channels/resistance thermom.; mV/mA
line frequency 50 Hz
single scanning
1)
cyclic scanning
line frequency 60 Hz
16 channels mV ; mA
result and sign
8 channels
channel 0 - 3
without
16 channels
channel 0 - 7
broken wire
8 channels
channel 4 - 7
detection
16 channels
channel 8 - 15
resistance thermometer
Inserting range cards
-1AA11
M +
Circuits
of the cards
4x
M -
Mode
æ 500 mV
500 mV/ mA
Pt 100
Pt 100
Mode
æ 50 mV
50 mV
9 - 78
Labelling of switches on the module cover:
I.
1)
It is advisable to mark the selected switch setting in these fields.
On one 465 analog input module, you can insert four cards for the
connection of four inputs each, and secure them with a screw.
There are voltage divider, shunt and through-connection cards for the
various ranges.
Range Card Type 6ES5 498-
-1AA21
-1AA31
M +
M +
M +
M -
M -
æ 1 V
æ 10 V
æ 20 mA
(æ 1 V)
(æ 2 mA)
(± 100 mV)
For a defined mode (50 mV or 500 mV), you can insert cards with
different ranges for every four inputs, e.g. for the 500 mV mode:
• • 4 inputs, range ± 500 mV; 1 card 6ES5 498-1AA11
• • 8 inputs, range ± 20 mA; 2 cards 6ES5 498-1AA41
Unused inputs must be short-circuited (with Pt 100 operation, this also
applies to the unused current outputs).
Note that the bus interface of the module is activated with 24 V via
enable lines F+ and F- at the front connector.
resistance thermometer
16 channels ...mV/ ...mA
50 mV
without compensation
1)
with compensation
500 mV/ ...mA/ resistance thermometer
8 channels ...mV/ ...mA/ resist.thermom.
voltage/current
-1AA41
-1AA51
-1AA61
M +
M +
L +
L -
M -
M -
M -
4 ... 20 mA
æ 5 V
2-wire trans.
(æ 500 mV)
-
C79000-B8576-C109-03
II.
-1AA71
M +
M -
4 ... 20 mA
4-wire trans.
-
System Manual

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

S5-135uSimatic s5