Siemens S5-155U System Manual page 47

Hide thumbs Also See for S5-155U:
Table of Contents

Advertisement

Wiring of Programmable Controllers for EMC
Figure 3-5
Examples of Securing Shielded Lines with Cable Clamps
3 - 18
Please observe the following points when connecting the shield:
• • Use metal cable clamps for securing the braided shield. The
clamps must enclose the shield over a large area and provide a
good contact.
• • Connect the shield to a shield bar immediately after the cable entry
into the cabinet. Route the shield as far as the module but do not
connect it there again.
System Manual
C79000-B8576-C199-03