6Es5 456-4Ub12 Digital Output Module - Siemens S5-155U System Manual

Hide thumbs Also See for S5-155U:
Table of Contents

Advertisement

8.4.15
6ES5 456-4UB12 Digital
Output Module
Rated supply voltage L
Number of outputs
Isolation
Range for supply voltage
Fusing
Output voltage
for logic 1
for logic 0
Residual current at logic 0
Switching current (resistive, inductive load)
ventilated
not ventilated
Switching current for lamps
ventilated
not ventilated
Contactor size
Max. inrush current for
≤ 3 ms
≤ 20 ms
≤ 50 ms
Switching capacity per module
for UL
for CSA
Permissible line length
Power supply
Digital section from system bus
Power dissipation (rated operation)
Enable input (F+/F-)
Voltage test to VDE 0160
Mechanical specifications
Dimensions (W x H x D)
Weight
System Manual
C79000-B8576-C199-03
115 to 230 V AC (47 to 63 Hz)
8, conditional short-circuit protection
Yes, 8 outputs
88 to 264 V AC
3.5 A fast, 1 fuse per outputs
L- 1.5 V min.
30 V max.
5 mA max.
40 mA to 2 A;
40 mA to 1 A;
40 mA to 2 A;
40 mA to 1 A;
0 (Type 3TB40) to 14 (Type 3TB58) at 230 V AC;
00 (Type 3TJ..) to 8 (Type 3TB52) at 115 V AC;
16 A
8 A
6.5 A
1440 VA max.
2000 VA max.
300 m max. unshielded
5 V, 100 mA typical
18.0 W
Jumper in front connector
Between two groups: 2000 V AC
Between group and ground point: 1500 V AC
40 mm x 255 mm x 195 mm
Approx. 0.6 kg
1) Protected by a fuse
2) Contactors of Series 3TJ can only be operated at 115 V AC.
Specification Sheets for the Modules
1)
2)
2)
8
8 - 63

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

S5-135uSimatic s5

Table of Contents