Siemens S5-155U System Manual page 330

Hide thumbs Also See for S5-155U:
Table of Contents

Advertisement

Common Technical Specifications
Operand identifiers
for inputs
for outputs
Parameters
Terminals
Rated DC voltage of module
Reference potential for DC voltage
Rated AC voltage of module
Reference potential for AC voltage
Permissible line length for
digital output modules
Enable inputs
Short-circuit signalling output
(only when the short-circuited
output is at logic 1)
Max. permissible supply voltage
for rated voltage 24 V DC (L+/L-)
for rated voltage 60 V DC (L+/L-)
for rated voltage 115 V/230 V AC (L/N)
Supply voltage ripple V
pp
referred to rated DC voltage
Interference suppression at digital inputs
Interference pulse length at digital outputs
Circuitry for inductive loads:
Switching of capacitive loads:
Safety tests
Surge voltage test to IEC 255-4
RFI test to IEC 255-4
Safety test for the -4UA13 modules
Immunity from conducted interference
on signal line
Immunity from discharge of static
electricity
8 - 32
I = Input
Q = Output
0.0 to 255.7
L+
L-
L
N
Allow for the line resistance and tolerance of the supply
voltage for the relevant output current.
F+
F-
(Enable voltage according to the rated voltage of the
module)
H+
(Supply for 1L+, referred to L- of the module)
1)
36 V DC for 100 ms
1)
90 V DC for 100 ms
276 V AC for 100 ms
2)
15 % max.
3)
≤ 1.5 ms
≤ 1.5 ms
3) 4)
Protective devices to limit the breaking voltage are
provided on the digital output modules. Additional
protective circuitry for the load is only required in
exceptional cases.
Exception: 458 digital output module
50 nF max. at full load
DC: Input/output to L-: V
AC: Input/output to L-: V
DC: Input/output to L-: V
AC: Input/output to L-: V
+
1 kV to IEC 801-4 (burst)
8 kV discharge in air to IEC 801-2
1) Supply and signal voltages must be produced as functional voltage with
safety separation.
2) The supply voltage range values are limit values. They include ripple.
3) If not otherwise specified
4) Must be bridged by the signal receiver
= 1 kV, 1.2/50 µs
p
= 2.5 kV, 1.2/50 µs
p
= 1 kV, 1 MHz
p
= 2.5 kV, 1 MHz
p
System Manual
C79000-B8576-C199-03

Hide quick links: