9.3.15

Technical Specifications

Rated input ranges with cards
for every 4 channels
- 6ES5 498-1AA11
- 6ES5 498-1AA21
- 6ES5 498-1AA31
- 6ES5 498-1AA41
- 6ES5 498-1AA51
- 6ES5 498-1AA61
- 6ES5 498-1AA71
Number of inputs
Measured-value representation
Measuring principle
Isolation
Permissible potential difference between reference
potentials of sensors and the module (U
between sensors (channels)
Power supply
- digital section from system bus
- analog section from load voltage
- enabling for module F+/F-
- tripping current L+
Constant current source for Pt 100 connection I
Integration time
Encoding time per measured value
System Manual
C79000-B8576-C109-03
6ES5 460-4UA13 Analog Input Module
± 12.5 mV/± 50 mV/± 500 mV/Pt 100
± 1 V
± 10 V
± 5 mA/± 20 mA
4 to 20 mA for two-wire transducer
± 5 V
4 to 20 mA for four-wire transducer
8 voltage/current inputs or
8 resistance inputs (Pt 100)
13 bits (two's complement) or
12 bits + sign;
± 2048 units in rated range;
512 to 2560 units for
4 to 20 mA
Integrating
Yes
8 inputs tested with respect to 0 V at 500 V AC
25 V AC/60 V DC max.
) and
CM
5 V ± 5 %, 130 mA typical
24 V, approx. 150 mA
24 V, approx. 5 mA
24 V, approx. 5 mA
/I
2.5 mA, TC = 5 x 10
C+
C-
20 ms at 50 Hz, 16
60 ms at 50 Hz, 50 ms at 60 Hz
1)
Plus 20 mA max. per connected two-wire transducer.
The 460 Analog Input Module
-5
/K
2
/
ms at 60 Hz
3
9 - 31
9