S5-135U/155U Central Controller
Noise immunity, electromagnetic compatibility (EMC)
RFI suppression
Limit value class
Conducted interference on AC supply lines (230 V AC)
to IEC 801-4 (burst)
to IEC 801-5
between two lines (µs pulses)
to IEC 801-5
between line and ground (µs pulses)
DC supply lines (24 V supply) to IEC 801-4 (burst)
Signal lines (24 V DC) to IEC 801-4 (burst)
Signal lines (230 V AC) to IEC 801-4 (burst)
Immunity to discharge of static electricity to
IEC 801-2 (ESD)
Immunity to RF interference
Mechanical data
Mechanical requirements
Weight
Dimensions (W x H x D)
4 - 16
To VDE 0871
A
2 kV
1 kV
2 kV
1 kV
1 kV
2 kV
Immunity of 4 kV contact discharge (8 kV air
discharge) is ensured with proper installation
(see Chapter 3).
RF field to IEC 801-6
limit value class 3 (up to 200 MHz),
corresponds to 3 V/m
Installation in stationary equipment, subject to
vibration; installation on ships and in vehicles if
special installation rules are observed, but not
on the engine.
approx. 14 kg
482.6 x 432 x 310 mm
C79000-B8576-C199-03