Quick Installation Guide
00825-0100-4593, Rev BA
July 2009
S
4: C
TEP
ONFIGURE THE
Failure Mode Alarm Switch
1. Remove the housing cover.
2. Locate the failure mode switch (see Figure 3).
3. Move the switch to the desired alarm setting. To set the failure mode to high alarm,
position the switch toward "HI." To set the failure mode to low alarm, position the switch
to "LO."
4. Replace the housing cover.
Write-Protect Switch
In the "ON" position, the write-protect switch prevents changes to the configuration data.
1. Remove the housing cover.
2. Move the write-protect switch to the "OFF."
3. Verify transmitter configuration (see "Verify Transmitter Configuration").
4. Move the write-protect switch to the "ON."
5. Replace the housing cover.
Figure 3. Switch Locations
Failure Mode Switch
T
RANSMITTER
Write-Protection Switch
HI
Zero Adjustment
Buttons
Rosemount 1151