4-10 Executing Programs (Drive Program-
ming Function Selection)
There are two ways to execute programs after you transferred (downloaded) them to the inverter as
described below.
Executing Program via CX-Drive
Executing via CX-Drive is a convenient way to debug the created program.
Use
icon in the toolbar of the Drive Programming Editor to start the program. To stop the program,
use
icon. Note that executing program via the CX-Drive is enabled only when the following condi-
tions are met.
• When the CX-Drive is connected to the inverter.
Once the program is started, it does not stop even if the CX-Drive is disconnected. Therefore, when
executing the program, make sure that you can stop the inverter immediately by turning off the power
supply, etc.
• When the program in the CX-Drive matches the program in the inverter through verification after
compilation.
• The program stop is executed regardless of the program in the CX-Drive.
Executing Program in Applications
You execute the program by setting the inverter parameter, the Drive Programming Function Selection
(A017).
Once the program reaches "end" command after a series of processes was completed, the program is
not executed unless it is restarted.
To repeat the program, create a loop program so that the program does not reach "end" command.
If the Drive Programming function is stopped while the Motor is running, the Motor will be stopped
according to the setting for the Stop Selection (b091) (deceleration stop or free-run stop).
Parameter
Function name
No.
A017
Drive Programming
Function Selection
Drive Programming User's Manual (I580-E2)
Data
00: Disabled (default setting)
01: Enabled (Start/stop via
multi-function input PRG
terminal)
02: Enabled
(Start/stop at power on/off)
4 Drive Programming Editor
Description
Disables the Drive Programming function.
Programs are not executed.
If you change the setting to 00 (Disabled)
during program execution, the program
will be stopped.
The Drive Programming program is
started when the multi-function input ter-
*1
minal
set to 82 (PRG) is turned ON.
Starts the Drive Programming program
automatically after the inverter power sup-
ply is turned on.
If you change the setting to 02 (Enabled)
while the program is stopped, the program
will be started.
4
4 - 25