6 Drive Programming Commands
func  value
Command
Assigns <value> to the multi-function input
variable.
 Example
In the above example, the following operation is repeated: a forward operation is performed at 60.00 Hz
until X(01) changes to ON. Then, a reverse operation is performed until X(02) changes to ON.
Block number
1
Sets the output frequency to 60.00 Hz.
2
Operates the inverter in the forward direction.
3 to 5
Waits until X(01) changes to ON, stops the inverter and waits with the "wait" command until the
inverter completely stops.
6
Operates the inverter in the reverse direction.
7 to 9
Waits until X(02) changes to ON, stops the inverter and waits with the "wait" command until the
inverter completely stops.
10
Jumps to the block 2: loop_ unconditionally.
6 - 40
Description
Flowchart method
<function> :
<value>
Flowchart
Function: any function bit of the multi-function
input variable (refer to 5-6 Multi-function Input
Variables on page 5-17 for details on each bit.)
Value: any variable or constant
Format
Text language method
<function> :  <value>
Operation
Drive Programming User's Manual (I580-E2)
Argument
Text