var Xw
Command
Assigns the status of the input terminal variable
to <variable> in units of words.
Note The input terminal variable is a variable that detects the status of the inverter's input terminal.
MX2:
Set the Multi-function Input S1 to S7 Selection (C001 to C007) to 56 to 62 (MI1 to MI7: General-purpose input).
Set the Pulse Train Input RP Selection (P003) to 02 (MI8: General-purpose input 8 for Drive Programming).
RX:
Set the Multi-function Input S1 to S8 Selection (C001 to C008) to 56 to 63 (MI1 to MI8: General-purpose input).
When the data is assigned in units of words, zero is read out for the upper byte data and unset input terminal variables.
<Assignment example>
X(00) MI1 (function No. 56) to Xw 1 (bit 0)
X(01) MI2 (function No. 57) to Xw 2 (bit 1)
X(02) MI3 (function No. 58) to Xw 4 (bit 2)
X(03) MI4 (function No. 59) to Xw 8 (bit 3)
X(04) MI5 (function No. 60) to Xw 16 (bit 4)
X(05) MI6 (function No. 61) to Xw 32 (bit 5)
X(06) MI7 (function No. 62) to Xw 64 (bit 6)
X(07) MI8 (MX2: P003 02/RX: function No. 63) to Xw 128 (bit 7)
For details, refer to 5-2 Input/Output Terminal Variables on page 5-5.
Example
In the above example, the status of the input terminals X(02) to X(05) is captured and output to the output terminals Y(00) to Y(03).
Block number
1
Assigns the value of Xw (value of input terminal) to U(00).
2
Divides the value of U(00) by 4 (2-bit right shift) to assign X(02) to bit 0.
3
Performs a logical AND operation on U(00) and 15 (binary: 00001111) and changes the bits higher than X(06) to zero.
4
Assigns U(00) to Yw.
5
Jumps to the block 1: loop_ unconditionally.
Drive Programming User's Manual (I580-E2)
Description
Flowchart method
<variable> :
Xw
The following settings are required. The numerical order of input terminal variables follows the
numerical order of the set general-input numbers.
Flowchart
6 Drive Programming Commands
Variable: any variable
Format
Text language method
<variable> : Xw
Operation
Argument
Text
6 - 37