Advertisement

5 Drive Programming User Variables
Function
variable
ERR-CNT
Fault Counter (d080)
Use this function to monitor the inverter's total number of faults. The monitored data is equivalent to the
data of the Fault Counter (d080). This variable is read-only.
Function
variable
ERR(1) to
Fault Monitor 1 to 6 (d081
ERR(6)
to 086)
Use this function to monitor the data of the last six trips of the inverter. The monitored data is equivalent
to the data of the Fault Monitor 1 to 6 (d081 to 086). This variable is read-only. The trip data is displayed
with a code, which is the same as that in the Inverter Fault Monitor Factor List used in the inverter's
Modbus communications.
Function
variable
DCV
DC Voltage Monitor
(d102)
Use this function to monitor the inverter's internal DC voltage. The monitored data is equivalent to the
data of the DC Voltage Monitor (d102). This variable is read-only.
Function
variable
STATUS
Inverter status monitor
Use this function to monitor the inverter's status.
Each bit corresponds to the following status. This variables is read-only.
5 - 16
Description
Data range
0 to 65,535
Description
Data range
0 to 127
Description
Data range
0 to 10,000
Description
Data range
Default
data
Times
Default
data
Default
data
0.1 V
Default
data
bit 0: Run
bit 1: Trip
bit 2: Reserve
bit 3: Retry
bit 4: Overload suppression
bit 5: Overcurrent suppression
bit 6: Overvoltage suppression
bit 7: Reset
bit 8: Undervoltage
bit 9 to 15: Reserve
Drive Programming User's Manual (I580-E2)
Unit
Data size
R/W
Unsigned
R
1 word
Unit
Data size
R/W
Unsigned
R
1 word
Unit
Data size
R/W
Unsigned
R
1 word
Unit
Data size
R/W
Unsigned
R
1 word