Connecting the V680S-A41@M/-A51@M Cable to the Host Device
 Power Supply and Operation Mode Signal
You must connect the power supply lines (24 VDC and 0 VDC) and the operation mode signal line in
the V680S-A41@M/-A51@M Cable.
Wire color
Meaning
Brown
24 VDC
Blue
0 VDC
Control signal
Violet
Note: If you start the Reader/Writer with the control signal connected to the -VDC side of the
power supply, the Reader/Writer will start in Safe Mode.
Refer to Safe Mode in Section 9 Troubleshooting for information on Safe Mode.
p.251
Connect the three terminals correctly. Otherwise, the Reader/Writer may be damaged.
 Power Supply
Use a power source that meets the following conditions.
Conditions
Power supply voltage
24 VDC -15% to +10%
500 mA DC or higher
 Connecting the Host Device
Connect the RJ45 connector on the V680S-
A41@M/-A51@M Cable to an Ethernet port on the
host device.
Press in the connector until it locks into place.
Use a device supporting STP cables for the host
device (such as a Switching Hub or PLC) which is
connected the specified Cables (V680S-A41 @M/-
A51 @M). Ground the host device to a ground
resistance of 100 Ω or less.
Connected to
+V DC output terminal
-V DC output terminal
Run Mode: +V DC output terminal
Safe Mode: -V DC output terminal*
Output current
Safety directive
UL Class 2
Installation and Connections
Applicable wire
AWG20
AWG24
RFID System
Section 4
83
User's Manual
(Modbus TCP)