20
communication. Refer to the Firmware Manual of the drive for
information on the communication settings. With an ACS550
drive, set parameter 98.02 COMM PROT SEL to EXT FBA.
With an ACS800, set parameter 98.02 COMM. MODULE LINK
to FIELDBUS and parameter 98.07 COMM PROFILE to ABB
DRIVES or GENERIC according to the selected communication
protocol and profile.
Table 1. Possible protocol and profile combinations
Communication protocol
Modbus/TCP
PROFINET IO
PROFINET IO
• If the configuration is correct, parameter group 51 should
appear in the parameter list of the drive and show the status of
the RETA-02 configuration parameters.
• Select communication protocol with a configuration parameter
51.16 'PROTOCOL'

Network configuration

To enable communication through the Ethernet network, the
module needs a valid IP address. There are numerous ways of
setting the module IP address; see chapter
• One way to set the static IP address is to use the panel of the
drive. Set IP address to bus configuration parameters 51.04 -
51.07, subnet mask to parameters 51.08 - 51.11 and gateway
address to parameters 51.12 - 51.15 if necessary. Set bus
configuration parameter 51.27 to REFRESH to enable the
network settings.
• If PROFINET IO protocol is activated also device name is
required to identify the drive. IO controllers and some
configuration tools have a protocol called Discovery and
Quick start-up guide
Communication profile Drive profile
ABB Drives profile
Vendor profile
PROFIdrive profile
0 =
Modbus/TCP
1 =
PROFINET IO
ABB Drives profile
ABB Drives profile
Generic drive profile
Network
configuration.