KEB COMBIVERT F5 Instruction Manual page 31

Housing b, 0.37...2.2 kw, 230v, 0.37...4.0kw, 400v
Hide thumbs Also See for COMBIVERT F5:
Table of Contents

Advertisement

• Integral solid state short circuit protection does not provide branch
circuit protection. Branch circuit protection must be provided in ac-
cordance with the Manufacturer Instructions, National Electrical Code
and any additional local codes, or the equivalent.
Branch Circuit Protection for inverters F5–B housing:
Inverter
05F5
05F5
07F5
07F5
09F5
09F5
10F5
10F5
12F5
#1) The voltage rating of the Class rated fuses shall be at least equal to the voltage rating of the
Drives.
Branch Circuit Protection: Type E Self Protected Manual Motor Controllers for inverters F5–B
housing.
Type and manufacturer and electrical ratings as specified below:
Cat. No.
Drive input rating
05F5
240V/1ph
05F5
240V/3ph
07F5
240V/1ph
07F5
240V/3ph
09F5
240V/1ph
09F5
240V/3ph
10F5
240V/1ph
10F5
240V/3ph
Input Voltage
[V]
240 / 1ph
240 / 3ph
480 / 3ph
240 / 1ph
240 / 3ph
480 / 3ph
240 / 1ph
240 / 3ph
480 / 3ph
240 / 1ph
240 / 3ph
480 / 3ph
480 / 3ph
Self Protected Manual Motor Con-
troller Type and manufacturer
PKZMO–10E, Eaton Industries
PKZMO–6.3E, Eaton Industries
PKZMO–16E, Eaton Industries
PKZMO–10E, Eaton Industries
PKZMO-20E, Eaton Industries
PKZMO–16E, Eaton Industries
PKZMO–32E, Eaton Industries
PKZMO–16E, Eaton Industries
Annex B
UL248 Fuse Class CC, J or
RK5 #1)
[A]
10
6
5
15
10
6
20
15
10
30
25
12
15
Self Protected Manual
Motor Controller rating
230V/ 1ph, 1.5 hp
230V/ 3ph, 1.5 hp
230V/ 1ph, 2 hp
240V/ 3ph, 3 hp
230V/ 1ph, 3 hp
230V/3ph, 5 hp
230V/ 1ph, 5 hp
230V/3ph, 5 hp