2.38 ~AA5PPSS

Description : Set PowerOn Value and Safe Value
Syntax : ~AA5PPSS[CHK](cr)
~
delimiter character
AA
address of setting module (00 to FF)
5
command for setting PowerOn Value and Safe Value
PP
PowerOn Value, 00=DO0 off, DO1 off, 01=DO0 on, DO1
off, 02=DO0 off, DO1 on, 03=DO0 on, DO1 on
SS
Safe Value, data format is same as PP
Response :
Invalid Command :
Syntax error or communication error may get no re-
sponse.
!
delimiter for valid command
?
delimiter for invalid command
AA
address of response module(00 to FF)
Example :
Command : ~0150003
Set address 01 PowerOn Value is DO0 off, DO1 off, Safe Value
is DO0 on, DO1 on, return success.
Related Command :
Sec.2.37 ~AA4
Related Topic :
Sec.3.2 Module Status, Sec.3.3 Dual Watchdog Operation
Note : The command is for I-7011/11D/11P/11PD only