2.22 @AADO(Data)

Description : Set Digital Output
Syntax : @AADI[CHK](cr)
@
delimiter character
AA
address of setting module (00 to FF)
DO
command for setting digital output
(Data)
output value, 00=DO0 off, DO1 off, 01=DO0 on, DO1
off, 02=DO0 off, DO1 on, 03=DO0 on, DO1 on
Response :
Invalid Command :
Syntax error or communication error may get no re-
sponse.
!
delimiter for valid command
?
delimiter for invalid command. While the alarm is en-
abled, the command will return invalid.
AA
address of response module(00 to FF)
Example :
Command : @01DO00
Set address 01 digital output 00, return success.
Related Command :
Sec.2.21 @AADI, Set.2.23 @AAEAT, Sec.2.26 @AADA
Related Topic :
Sec.3.5 Digital Output
Note : The command is for I-7011/11D/11P/11PD only