2.19 ~AAO(Data)

Description : Set Module Name
Syntax : ~AAO(Data)[CHK](cr)
~
delimiter character
AA
address of setting module (00 to FF)
O
command for setting module name
(Data)
new name for module, max 6 characters
Response :
Invalid Command :
Syntax error or communication error may get no re-
sponse.
!
delimiter for valid command
?
delimiter for invalid command
AA
address of response module(00 to FF)
Example :
Command : ~01O7018
Set address 01 module name to 7018, return success.
Command : $01M
Read address 01 module name, return 7018.
Related Command :
Sec.2.17 $AAM
40
Valid Command :
I-7011, I-7018 User Manual
!AA[CHK](cr)
?AA[CHK](cr)
Receive : !01
Receive : !017018