Aab - ICP DAS USA Network Device I-7011 User Manual

B&b electronics network device user manual
Table of Contents

Advertisement

2.15 $AAB

Description : Thremocouple Open Detection
Syntax : $AAB[CHK](cr)
$
delimiter character
AA
address of reading module (00 to FF)
B
command for reading thremocouple open status
Response :
Invalid Command :
Syntax error or communication error may get no re-
sponse.
!
delimiter for valid command
?
delimiter for invalid command
AA
address of response module(00 to FF)
S
0=close-loop detection
1=open-circuit detection, need to check the thermocouple
Example :
Command : $01B
Read address 01 thermocouple open status, return the thermo-
couple is close-loop.
Note : The command is for I-7011/11D/11P/11PD only
36
Valid Command :
I-7011, I-7018 User Manual
!AAS[CHK](cr)
?AA[CHK](cr)
Receive : !010
Rev:B1.0

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

I-7011dI-7011pI-7011pdI-7018I-7018p