2.25 @AALO(Data)

Description : Set Low Alarm
Syntax : @AADI[CHK](cr)
@
delimiter character
AA
address of setting module (00 to FF)
LO
command for setting high alarm value
(Data)
high alarm values, data format is in engineer unit format.
Response :
Invalid Command :
Syntax error or communication error may get no re-
sponse.
!
delimiter for valid command
?
delimiter for invalid command
AA
address of response module(00 to FF)
Example :
Command : @01LO-2.5000 Receive : !01
Set address 01 low alarm -2.5000, return success.
Related Command :
Sec.2.23 @AAEAT, Sec.2.29 @AARL
Related Topic :
Sec.3.6 High/Low Alarm
Note : The command is for I-7011/11D/11P/11PD only
Rev:B1.0
Valid Command :
I-7011, I-7018 User Manual
!AA[CHK](cr)
?AA[CHK](cr)
47