Analog input type and data format table
Type
Input Range
Code
-15 to +15
00
mV
-50 to +50
01
mV
-100 to +100
02
mV
-500 to +500
03
mV
Rev:B1.0
Data Format
Engineer Unit
% of FSR
2's complement HEX
Engineer Unit
% of FSR
2's complement HEX
Engineer Unit
% of FSR
2's complement HEX
Engineer Unit
% of FSR
2's complement HEX
I-7011, I-7018 User Manual
Engineer Unit
+F.S.
Zero
+15.000 +00.000 -15.000
+100.00 +000.00 -100.00
7FFF
0000
+50.000 +00.000 -50.000
+100.00 +000.00 -100.00
7FFF
0000
+100.00 +000.00 -100.00
+100.00 +000.00 -100.00
7FFF
0000
+500.00 +000.00 -500.00
+100.00 +000.00 -100.00
7FFF
0000
+1.0000 +0.0000 -1.0000
-F.S.
8000
8000
8000
8000
17