IEC 61800-3:2004 and EN 61800-3:2004
The 2004 revision of the standard uses different terminology to align the requirements of the
standard better with the EC EMC Directive.
Power drive systems are categorized C1 to C4:
Category
C1
Intended for use in the first or second environments
Not a plug-in or movable device, and intended for use in
C2
the first environment only when installed by a
professional, or in the second environment
Intended for use in the second environment, not the first
C3
environment
Intended for use in the second environment in a system
C4
rated at over 400A, or in a complex system.
Note that category 4 is more restrictive than E2R, since the rated current of the PDS must exceed
400 A or the supply voltage exceed 1000 V, for the complete PDS.
5.2

Optional external EMC filters

Table 5-34 EMC filter cross reference
Model
200 V
03200050 to 03200106
04200137 to 04200185
400 V
03400025 to 03400100
04400150 to 04400172
5.2.1
EMC filter ratings
Table 5-35 Optional external EMC filter details
Maximum
continuous
current
Part
number
@ 40 °C
@ 50 °C
(104 °F)
(122 °F)
A
4200-3230
20
4200-0272
27
4200-3480
16
4200-0252
25
96
Definition
Voltage
rating
IP
rating
IEC
UL
A
V
V
18.5
250
300
24.8
250
300
20
15
528
600
23
528
600
Unidrive M/HS Frame 3 and 4 Power Installation Guide
CT part number
4200-3230
4200-0272
4200-3480
4200-0252
Power
Ground leakage
dissipation at
Balanced
rated current
supply
phase-to-
@ 40 °C
@ 50 °C
phase and
(104 °F)
(122 °F)
phase-to-
ground
W
W
mA
20
17
2.4
33
28
6.8
13
11
10.7
28
24
11.1
Corresponding code
used above
R
I
E2U
E2R
Discharge
Worst
resistors
case
mA
MΩ
60
137
1.68
151
182
Issue Number: 3