Table 4-2 2 % line reactors
Voltage
Drive
Line reactor
rating
model
designation
number
V
03200050
200
03200066
200
03200080
200
03200106
200
04200137
200
04200185
200
03400025
400
03400031
400
03400045
400
03400062
400
03400078
400
03400100
400
04400150
400
04400172
400
4.2.3
Input inductor calculation
To calculate the inductance required (at Y %), use the following equation:
Y
V
1
L
--------- -
------ -
----------- -
=
×
×
100
2πfI
3
Where:
I = drive rated input current (A)
L = inductance (H)
f = supply frequency (Hz)
V = voltage between lines
4.3

Supplying the drive with DC

All drive sizes have the option to be powered from an external DC power supply. Refer to section
4.1 Power and ground connections on page 46 to identify the location of DC supply connections.
The DC supply connections for size 3 and 4 are located under the DC / Braking terminal cover.
Figure 4-3 shows DC supply connections and cable routing.
50
CT Part
number
INL2001
4401-0143
INL2001
4401-0143
INL2002
4401-0144
INL2002
4401-0144
INL2002
4401-0144
INL2003
4401-0145
INL4001
4401-0148
INL4001
4401-0148
INL4002
4401-0149
INL4011
4401-0234
INL4011
4401-0234
INL4003
4401-0151
INL4004
4401-0152
INL4005
4401-0153
Unidrive M/HS Frame 3 and 4 Power Installation Guide
Line
reactor
Inductance
Weight
current
rating
A
mH
13.5
0.79
13.5
0.79
20.6
0.48
20.6
0.48
20.6
0.48
26.8
0.32
6.6
2.94
6.6
2.94
9.1
1.62
13
1.12
13
1.12
15.8
1.05
18.7
0.79
24.3
0.61
Length Width
kg
mm
mm
1.8
156
70
1.8
156
70
2.4
156
80
2.4
156
80
2.4
156
80
2.5
156
80
1.3
80
75
1.3
80
75
1.8
156
70
2.5
156
80
2.5
156
80
2.6
156
80
3.5
156
60
4.9
156
75
Issue Number: 3