Emerson Unidrive M700 Installation Manual page 72

Frame 3 to 4
Hide thumbs Also See for Unidrive M700:
Table of Contents

Advertisement

Figure 4-19 Shielding requirements of optional external braking resistor
Enclosure
If the control wiring is to leave the enclosure, it must be shielded and the shield(s) clamped to the
drive using the grounding bracket as shown in Figure 4-20. Remove the outer insulating cover of the
cable to ensure the shield(s) make direct contact with the bracket, but keep the shield(s) intact until
as close as possible to the terminals. Alternatively, wiring may be passed through a ferrite ring, part
number 3225-1004.
Figure 4-20 Grounding of signal cable shields using the grounding bracket
72
Optional external
braking resistor
BR
+DC
OR
Unidrive M/HS Frame 3 and 4 Power Installation Guide
Optional external
braking resistor
Enclosure
BR
+DC
Issue Number: 3

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Unidrive hs72Unidrive m600Unidrive hs70

Table of Contents