Cable layout
Figure 4-14 indicates the clearances which should be observed around the drive and related 'noisy'
power cables by all sensitive control signals / equipment.
Figure 4-14 Drive cable clearances
Do not place sensitive
(unscreened) signal circuits
in a zone extending
300 mm (12") all around the
Drive, motor cable, input
cable from EMC filter and
unshielded braking resistor
cable (if used)
N
NOTE
Any signal cables which are carried inside the motor cable (i.e. motor thermistor, motor brake) will
pick up large pulse currents via the cable capacitance. The shield of these signal cables must be
connected to ground close to the motor cable, to avoid this noise current spreading through the
control system.
68
300 mm
(12 in)
Unidrive M/HS Frame 3 and 4 Power Installation Guide
Optional braking resistor and overload
Issue Number: 3