Maintenance; Optional Controls - Emerson FieldQ QC4124 V DC Installation Manual

Integrated control modules
Table of Contents

Advertisement

Installation Guide
DOC.IG.QC41.1 Rev. 4
Procedure (see Figure 5.3):
1. Remove cover (15) and loosen the screw (11) of
the shield (12) and turn the shield down.
Closed Position:
2. Move the actuator/valve assembly to the closed
position by removing the control signal from
terminal 8 and 9 (see § 4.1).
3. Turn top screw (10) counter clock wise maximum
20 turns, (do not force the adjustment screw)
until the switch trips to the "off state" (no signal).
4. Turn top screw (10) clock wise 1 3/4 turn (do not
force the adjustment screw).
The "closed" position switch point is now set to
factory setting.
Open Position:
5. Move the actuator to the open position by
applying the applicable voltage to terminal 8
and 9 (see § 4.1).
6. Turn bottom screw (9) clock wise maximum
20 turns, (do not force the adjustment screw)
until the switch trips to the "on state" (no signal).
7. Turn bottom screw (9) counter clock wise 1 3/4
turn (do not force the adjustment screw)
The "open" position switch point is now set to
factory setting.
8. Turn the shield (12) back over the adjustment
screws and fasten it with the screw (11) and
mount cover (15) back in place.
IMPORTANT
Do not force the adjustment screws
During switch point adjustment, do not force the
adjustment screws when you feel an obstruction.
Forcing the adjustment screws can damage the
cross head of the adjustment screw.

7 Maintenance

The FieldQ Control Modules are designed to
operate without maintenance. For any further
maintenance to the actuator see Installation and
Operation Manual FieldQ Valve Actuator, DOC.
IOM.Q.E or contact your local FieldQ representative.
Installation, adjustment, putting into service, use,
assembly, disassembly, maintenance and repair
of the Control Module must be done by qualified
personnel.
Note:
This product is only intended for use in large-scale
fixed installations excluded from the scope of
Directive 2011/65/EU on the restriction of the use
of certain hazardous substances in electrical and
electronic equipment (RoHS 2).

8 Optional Controls

8.1 Manual Control options
(see Figure 8.1)
For commissioning, emergency or maintenance
purposes, the FieldQ can be supplied with one or
two Manual Control options. These can operate the
pilot valve(s) inside the module and as such operate
the actuator, when there is air pressure available,
but no control signal or power supply.
Lock
Unlock
45°
On
Off
Fig. 8.1 Local Manual Control options
8.1.1 Mounting Manual Control
1 To add a Manual Control, remove the plug(s)
in front of the module and turn in the Manual
Control.
-
For normal operation the module should be
fitted with one Manual Control.
-
For Double Acting with a Fail-in-Last-Position
function, two Manual Control can be fitted.
FieldQ
April 2020
Location for 2nd
Manual Control
Default location
of Manual Control
17