Section 10: Annex A
October 2022
Section 10:
10.1
Replacement of 494MOD1000 with
494MOD1200
XTE3000 Modbus RTU module can be mounted only on base card revision 6.03 or subsequently.
When a user needs to replace an older 494MOD1000 card with a new 494MOD1200 module, it's
necessary to provide the following operations:
•
Figure 11
•
•
Figure 12
52
Installation, Operation and Maintenance Manual
Annex A
Disconnect the 494MOD1000 card from the cable linked to the terminal board
(see the Figure below).
Remove the 494MOD1000 interface card.
Cut the cable to have all the six wires available (1 shield and 2 signals for each channel):
VCIOM-15081-EN Rev. 7
Shield
Shield
Annex A