inverters
Goodrive200
Functio
Name
n code
ratio of the
dropping
control
P08.31
Reserved
FDT1
electrical
P08.32
level
detection
value
FDT1
retention
P08.33
detection
value
FDT2
electrical
level
P08.34
detection
value
FDT2
retention
P08.35
detection
value
P08.36
Frequency When the output frequency is among the below or 0.00Hz
Detailed instruction of parameters
when several inverters drive one load.
Setting range:0.00~10.00Hz
When
the
output
corresponding frequency of FDT electrical level, the
multi-function digital output terminals will output the
signal of "frequency level detect FDT" until the output
frequency decreases to a value lower than (FDT
electrical level—FDT retention detection value) the
corresponding frequency, the signal is invalid. Below
is the waveform diagram:
Setting range of P08.32: 0.00Hz~P00.03(the Max.
frequency)
Setting
range
of
electrical level)
Setting range of P08.34: 0.00 Hz ~P00.03(the Max.
frequency)
Setting range of P08.35: -100.0%~100.0%(FDT2
electrical level)
frequency
exceeds
P08.33:
0.0~100.0%(FDT1
96
Function codes
Default
Modify
value
◎
0
the
○
50.00Hz
○
5.0%
○
50.00Hz
○
5.0%
○