8.1.3 Configuration

• For using the capture function or sampling capture function, set the following items using the
configuration menu of tool software or user programs.
• Set the signal allocated to the trigger signal for executing capturing and the number of
operations. For the sampling capture, also set the sampling time.
 Setting area
Unit
memory
Name
No.
(Hex)
UM 00110
UM 001E0
Capture 0
setting
UM 002B0
UM 00380
UM 00111
UM 001E1
Capture 1
setting
UM 002B1
UM 00381
UM 00112
Capture
UM 001E2
function
operation
UM 002B2
setting
UM 00382
UM 00113
UM 001E3
Sampling time
UM 002B3
UM 00383
(Note 1) The unit memory numbers in the above table are for CH0, CH1, CH2 and CH3 from the top.
next page
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Default
Setting range and description
Make the setting for the capture function or sampling capture
function.
H0: Not use capture 0 function
H1: Capture function at rising edge of control 0 signal
H2: Capture function at trailing edge of control 0 signal
H3: Capture function at rising edge of control 1 signal
H0
H4: Capture function at trailing edge of control 1 signal
H5: Control 0 signal positive logic sampling capture function
H6: Control 0 signal negative logic sampling capture function
H7: Control 1 signal positive logic sampling capture function
H8: Control 1 signal negative logic sampling capture function
H9: Output relay (Y relay) sampling capture function
Make the setting for the capture function or sampling capture
function.
H0: Not use capture 1 function
H1: Capture function at rising edge of control 0 signal
H0
H2: Capture function at trailing edge of control 0 signal
H3: Capture function at rising edge of control 1 signal
H4: Capture function at trailing edge of control 1 signal
However, this setting area is invalid when the sampling capture
function (H5 to H9) is selected in the capture 0 setting.
Make the setting for the capture function or sampling capture
function.
H0
H0: One operation
H1: Continuous operation
Set the sampling time for using the sampling capture function.
1
Setting range: 1 to 65,535 (The values out of the setting range
are invalid.)
Unit
-
-
-
ms