10.1.3 Clearing Errors Using User Programs

• Each error can be cleared by user programs.
• Refer to error codes, correct error factors, and clears the errors.
 Clearing all channels by UCLR instruction
• Executing the dedicated instruction UCLR (error) clears errors occurred in the high-speed
counter unit.
Example) Program to clear errors of the high-speed counter unit installed in the slot No. 1
R100
DF
Unit clear
request
 Clearing each channel separately by I/O signals
• Turning on the error clear request flag allocated to the I/O area clears errors in each channel
separately. The program below shows the error clear of channel 0.
• The overflow or underflow annunciation flag can be cleared by each clear signal, reset or
preset operation. However, error states are not cleared.
Example) Program to request for clearing errors of CH0 of the high-speed counter unit
installed in the slot No. 1
R100
DF
Error clear
request
Y10F
CH0 error
clear request
 Allocation of I/O signals
Signal name
Overflow clear
Underflow clear
Error clear
Overflow annunciation
Underflow annunciation
Error annunciation
(Note 1): The above I/O numbers are those for the slot number 1 and the starting word number 10. The I/O numbers
actually used vary according to the slot number where the unit is installed and the starting word number.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
X10F
CH0 error
annunciation flag
UCLR
U1
Slot No.
Y10F
CH0 error
clear request
CH0
CH1
Y10D
Y11D
Y10E
Y11E
Y10F
Y11F
X10D
X12D
X10E
X12E
X10F
X12F
CH2
CH3
Y12D
Y13D
Y12E
Y13E
Y12F
Y13F
X14D
X16D
X14E
X16E
X14F
X16F

Advertisement

Table of Contents
loading

Table of Contents