High-speed counter unit
Hide thumbs Also See for FP7:
Table of Contents

Advertisement

KEY POINTS
For using the Z-phase signal, control signal or comparison match flag as
reset signals, turn on the reset enable request signal using user programs.

5.3.2 Preset Input

The following three preset methods are available.
 Type of reset signals
Preset
Setting method
element
Output Y
Activates the preset request signal by a user
relay
program.
Input Z
Allocates the Z-phase input signal to either preset
signal
operation using the configuration menu.
Allocates the control 0 signal to either reset
operation using the configuration menu.
Control 0
Positive logic enable operation and preset
signal
operation at rising edge
Negative logic enable operation and preset
operation at trailing edge
 I/O Allocation
Signal name
Preset request
Input Z signal monitor
Control 0 signal monitor
(Note 1): The above I/O numbers are those for the slot number 1 and the starting word number 10. The I/O numbers
actually used vary according to the slot number where the unit is installed and the starting word number.
 Setting of preset values
Unit
memory
Name
No.
(Hex)
UM 00062
UM 00063
UM 00132
UM 00133
Preset
value
UM 00202
UM 00203
UM 002D2
UM 002D3
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Effective
condition
ON edge
-
-
Default
Set preset values.
Setting range:
0
-2,147,483,648 (8000 0000H) to 2,147,483,647 (7FFF FFFFH)
Signed 32-bit
Preset condition
ON
OFF
CH0
Y103
X10A
X10B
Setting range and description
ON
ON
ON
OFF
OFF
OFF
CH1
CH2
CH3
Y113
Y123
Y133
X12A
X14A
X16A
X12B
X14B
X16B
Unit