10.2.2 Errors Occurred in Operations (1000H to 1043H)

• These are errors occurred in operations.
• Take steps according to the contents in the table below.
 List of error codes
Error
Channel
code
No.
1000H
CH0
1001H
CH1
1002H
CH2
1003H
CH3
1010H
CH0
1011H
CH1
1012H
CH2
1013H
CH3
1020H
CH0
1021H
CH1
1022H
CH2
1023H
CH3
1030H
CH0
1031H
CH1
1032H
CH2
1033H
CH3
1040H
CH0
1041H
CH1
1042H
CH2
1043H
CH3
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Error name
Content
The count value
Overflow error
exceeds the upper
limit.
The count value
Underflow error
exceeds the lower
limit.
The count value
becomes 0 under the
reset condition, and it
Reset error
is outside the range of
upper and lower
limits.
The count value is
outside the range of
Preset error
upper and lower limits
under the preset
condition.
The count value is
outside the range of
Current value
upper and lower limits
change error
when the current
value is changed.
Operation
Countermeasures
Performs the reset or
Announces the
preset operation to
overflow error. Holds
make the count value
the count value.
be in the range of
upper and lower limits.
Performs the reset or
Announces the
preset operation to
underflow error. Holds
make the count value
the count value.
be in the range of
upper and lower limits.
Confirm the settings of
the upper and lower
Does not reset.
limits of counter. If 0
Continues the count
does not exist in the
operation.
range of the upper and
lower limits, make the
preset request.
Confirm if the specified
Does not preset.
preset value is in the
Continues the count
range of upper and
operation.
lower limits.
Does not change the
Confirm if the current
current value.
value changed value is
Continues the count
in the range of upper
operation.
and lower limits.

Advertisement